ja_mageia

More info please contact us!
The main introductions and parameters of our products are all in our website,if you want to know more,or need any help for the products,please feel free to contact us!
  • Narrow screen resolution
  • Wide screen resolution
  • Decrease font size
  • Default font size
  • Increase font size
Home FAQs FAQs How to select a refrigerated dryer?
How to select a refrigerated dryer? PDF Print E-mail

How to select a refrigerated dryer?

  • The digital control modules are of standard configuration.

  • All models adopt standard-configured electronic instruction water dischargers.

  • To select a good refrigerated dryer, you must take into consideration the compressed air actual flow-rate, pressure, air inlet temperature, and the ambient temperature, as well as the required pressure dew point temperature (5 factors). The air treatment capacity of the dryer can be expressed by Qs = Qa x C1 x C2 x C3

product standard working conditions are formulated.

Inlet air temperature: 50? Ambient temperature: 40? Pressure dew point:3? Cooling mode: air cooling or water cooling
Refrigerant: R22 Inlet air pressure: 0.7Mpa Pressure loss: ≤0.02Mpa

Note: When inlet air temperature is higher that 65 ?, we recommand to use refrigerated air dryer with per cooler.

Refrigerated Air Dryer Volumetric Flow-Rate Correction Factors Table 1

Inlet air pressure Inlet air temperature
30 35 40 45 50 55 60 65 70 75 80 85 90 95
6 1.5 1.32 1.17 1.04 0.92 0.81 0.72 0.63 0.54 0.45 0.36 0.27 0.18 0.09
7 1.58 1.41 1.26 1.12 1 0.89 0.8 0.71 0.62 0.62 0.44 0.35 0.26 0.17
8 1.65 1.48 1.32 1.19 1.06 0.96 0.86 0.77 0.68 0.68 0.5 0.41 0.32 0.23
9 1.71 1.52 1.38 1.26 1.13 1.02 0.92 0.82 0.72 0.72 0.52 0.42 0.32 0.22
10 1.75 1.57 1.43 1.29 1.18 1.07 0.97 0.878 0.79 0.79 0.61 0.52 0.43 0.34

The above factors are derived from dew point temperature of 3? and ambient temperature of 40?

Dew Point Temperature Correction Factors Table 2

Dew point temperature 3? 5? 7? 10?
Correction Factors 1 1.233 1.435 1.711

The above factors are derived from air-inlet temp
erature of 50? and pressure of 7kg/cm2

Environment Temperature Correction Factors Table 3

Environment temperature? 30 35 40 43 50 54 57
Correction Factors 1.12 1.06 1 0.94 0.81 0.75 0.69

When ambient temperature is higher than 57 ?, we recommend to use water