How to select a refrigerated dryer?
-
The digital control modules are of standard configuration.
-
All models adopt standard-configured electronic instruction water dischargers.
-
To select a good refrigerated dryer, you must take into consideration the compressed air actual flow-rate, pressure, air inlet temperature, and the ambient temperature, as well as the required pressure dew point temperature (5 factors). The air treatment capacity of the dryer can be expressed by Qs = Qa x C1 x C2 x C3
product standard working conditions are formulated.
Inlet air temperature: 50? Ambient temperature: 40? Pressure dew point:3? Cooling mode: air cooling or water cooling
Refrigerant: R22 Inlet air pressure: 0.7Mpa Pressure loss: ≤0.02Mpa
Note: When inlet air temperature is higher that 65 ?, we recommand to use refrigerated air dryer with per cooler.
Refrigerated Air Dryer Volumetric Flow-Rate Correction Factors Table 1
| Inlet air pressure |
Inlet air temperature |
| 30 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
85 |
90 |
95 |
| 6 |
1.5 |
1.32 |
1.17 |
1.04 |
0.92 |
0.81 |
0.72 |
0.63 |
0.54 |
0.45 |
0.36 |
0.27 |
0.18 |
0.09 |
| 7 |
1.58 |
1.41 |
1.26 |
1.12 |
1 |
0.89 |
0.8 |
0.71 |
0.62 |
0.62 |
0.44 |
0.35 |
0.26 |
0.17 |
| 8 |
1.65 |
1.48 |
1.32 |
1.19 |
1.06 |
0.96 |
0.86 |
0.77 |
0.68 |
0.68 |
0.5 |
0.41 |
0.32 |
0.23 |
| 9 |
1.71 |
1.52 |
1.38 |
1.26 |
1.13 |
1.02 |
0.92 |
0.82 |
0.72 |
0.72 |
0.52 |
0.42 |
0.32 |
0.22 |
| 10 |
1.75 |
1.57 |
1.43 |
1.29 |
1.18 |
1.07 |
0.97 |
0.878 |
0.79 |
0.79 |
0.61 |
0.52 |
0.43 |
0.34 |
The above factors are derived from dew point temperature of 3? and ambient temperature of 40?
Dew Point Temperature Correction Factors Table 2
| Dew point temperature |
3? |
5? |
7? |
10? |
| Correction Factors |
1 |
1.233 |
1.435 |
1.711 |
The above factors are derived from air-inlet temp
erature of 50? and pressure of 7kg/cm2
Environment Temperature Correction Factors Table 3
| Environment temperature? |
30 |
35 |
40 |
43 |
50 |
54 |
57 |
| Correction Factors |
1.12 |
1.06 |
1 |
0.94 |
0.81 |
0.75 |
0.69 |
When ambient temperature is higher than 57 ?, we recommend to use water